What is regulation for fuel of Fire Pump on ships as per SOLAS?

Any service fuel tank shall contain sufficient fuel to enable the pump to run on full load for at least three hours and sufficient reserves of fuel shall be available outside the main machinery space to enable the pump to be run on full load for an additional 15 hours.

NOTE :

Any diesel driven power source for the pump shall be capable of being readily started in its cold condition down to a temperature of 0°C by hand (manual)cranking. If this is impracticable, or if lower temperatures are likely to be encountered, consideration is to be given to the provision and maintenance of heating arrangements, acceptable to the Administration.

These means shall be such as to enable the diesel driven power source to be started at least 6 times within a period of 30 minutes, and at least twice within the first 10 minutes.