Fixed high expansion foam fire extinguishing system:
- Generate foam for extinguishing oil fires.
- High expansion foam in machinery spaces shall fill at a rate of 1m in depth per min.
- Foam making liquid should be sufficient to produce a volume equivalent to five times the volume of the largest space.
- Max expansion ratio to be 1000 to 1.