What is SOLAS requirements for fixed fire detection and fire alarm system present on board?

SOLAS requirements for fixed fire detection and fire alarm system present on board:
  • The system should not be used for any other purpose except for closing of fire doors etc.
  • Zone address identification.
  • First initiated fire alarm shall not prevent any other detector to initiate further alarms.
  • Minimum 2 sources of power supply to the system.
  • Activation of any detector or a manually operated call point shall initiate a visual and audible alarm at the control panels.
  • If the alarm on the alarm panel is not acknowledged in 2 mins then general alarm shall sound.
  • Control panel to be placed on the bridge or the continuously manned control station.
  • When the bridge is unmanned, the alarm shall sound in a place where a responsible member of the crew is on duty.
  • Manually activated call points. One at each exit and max distance between 2 to be 20m.
  • Installed in periodically unmanned machinery spaces.
  • Where the main propulsion and associated machinery is present despite of being manned.